INPUT
Voltage Range ………………420VAC to 530VAC
Frequency ………………….………… 54 to 66 Hz
OUTPUT (TBAT = 25°C)
Voltage ………...…….……….… 74VDC Nominal
Output Current Range …………….. 0 to 150ADC
Output Voltage Ripple ….………………. < 1% F.S.
Efficiency.… …………….…………………….. 90%
ENVIRONMENTAL
Operating Temp. Range ……..…… -20°C to 50°C
Storage Temp. Range …….……. -40°C to +85°C
Humidity ….………… 0 to 95%, Non-Condensing
Cooling ………………...…………. Internal Blower
PHYSICAL SPECIFICATIONS
Dimensions, Inches …….. 18”W X 30”H X 8.25”D
Case Material .………….…….………….…... Steel
Finish .…..…………………... Epoxy Powder Coat
Color ……………….………………………… White
Input Connectors
J1 - Input Power
J2 - Communications Signals
J3 - Output Power
|
PROTECTION FEATURES
• LVPS/BC latches off in the event of input over voltage or phase loss
• LVPS/BC latches off if over temp is detected on any power semiconductor
• Output current limiting
• Over voltage, over current and over temp protection for IGBTs
• LVPS/BC opens a breaker to protect battery if a battery over temp is detected or if the battery will not take a charge
• If a fault is removed, the LVPS/BC can be reset via a front panel push-button
FRONT PANEL Displays and Status Indicators
Digital Voltmeter
Digital Ammeter
LED Normal Battery Voltage
LED Normal Input Voltage
LED Battery Over Temperature
LED LVPS/BC Failure
LED LVPS/BC Over Temperature
LED Low Battery Voltage
LED Over Current Latch
LED Phase Loss
|